Providing emergency eye wash and shower facilities for employees who work outdoors and are exposed to chemical hazards can be challenging during the winter months. Standard equipment will freeze when the mercury dips below 32F, rendering the station

by Other Author
Register for free to listen to this article
Listen with Speechify
0:00
5:00

Providing emergency eye wash and shower facilities for employees who work outdoors and are exposed to chemical hazards can be challenging during the winter months. Standard equipment will freeze when the mercury dips below 32F, rendering the station useless and creating an unsafe work environment.

According to the ANSI Z358.1-2004 Standard for Emergency Eye Wash and Shower Equipment, emergency wash systems must either be shielded from freezing or outfitted with freeze-protected equipment when the possibility of freezing exists.

Get training in Technical Safety Topics and earn CEUs.An IACET-accredited five-course stream in the Academy.
Technical Safety Topics Stream

Manufacturers of emergency eye wash and shower equipment have developed freeze-resistant and freeze-protected equipment to meet cold-weather needs. Both systems work well for their designed application. There are differences between the two styles, however, that dictate where each should be used.

Designed to withstand subfreezing conditions for brief periods, freeze-resistant systems remove any portion of the system containing water from direct exposure to the elements. Valves and piping that contain water are either located in a heated building or underground below the frost line. The eye wash heads, shower head and additional piping are placed outside, exposed to water only when the system is activated.

 

Special freeze-prevention valves may also be incorporated into the design. When these valves sense temperatures approaching 40F, they partially activate flow. They fully activate around 35F to move water in the system and prevent freezing.

When freeze-resistant systems are shut down after being activated, water will remain in the system where it can freeze and eventually cause damage. Freeze-prevention valves require a continuous water flow to prevent freezing. This wastes water and can be a slip hazard depending on the drain system in place. Because of these conditions, freeze-resistant systems are recommended for areas where subfreezing temperatures will be present for short periods only.

Freeze-protected systems are ideal for locations where temperatures are expected to drop below freezing for extended periods of time. These systems are electrically heat-traced and insulated for extreme cold weather. Manufacturers generally design systems to withstand temperatures well below 0F.

Heat-tracing cables and added insulation make freeze-protected equipment more expensive and a bit more complicated to install than freeze-resistant systems. For a majority of applications, freeze-protected systems are the only option.

Keep in mind that neither freeze-resistant nor freeze-protected systems, in their base design, are water-tempering systems. Water dispensed from both types will be the same temperature as the supply source.

LSS (Lab Safety Supply) provides Lab Managers with useful information and a huge selection of laboratory equipment, plastics, glassware, safety, spill clean-up and more. Call 800-356-0783 to request your FREE Lab Supplies Catalog or go online at LSS.com/labsupplies for 24/7 access to the over 130,000 products LSS has to offer! Lab Safety Supply Inc., Janesville WI, Reproduced with Permission.