Key takeaways
- NFPA 45, the Standard on Fire Protection for Laboratories Using Chemicals, classifies laboratory units from Class A (high fire hazard) to Class D (minimal) based on flammable and combustible liquid quantities.
- A Class A laboratory unit can hold up to 10 gallons of Class I flammable liquid per 100 square feet, or 20 gallons of Class I, II, and III liquids combined.
- Building and fire codes (IBC/IFC) separately cap hazardous materials per control area, and the allowance shrinks on higher floors.
- Labs must satisfy both: NFPA 45 itself requires inventories to stay within the maximum allowable quantities of the applicable fire or building code.
- Editions and local adoption vary, so confirm which versions apply to your building before relying on any number.
Flammable liquid limits in a lab don’t come from one rulebook. They come from two that overlap. NFPA 45 limits how much a laboratory unit can hold per square foot. The building and fire codes limit how much an entire control area can hold, and they cut that allowance sharply as you go up a building. On a typical first floor, a control area can use its full maximum allowable quantity; on the tenth floor and above, UW–Madison’s chemical storage guidelines show it dropping to 5%.
NFPA 45 is the Standard on Fire Protection for Laboratories Using Chemicals. It classifies labs by fire hazard, limits flammable and combustible liquid quantities, and sets storage, ventilation, and fire protection rules, while the IBC and IFC cap totals per control area by floor. A compliant lab satisfies both. This article explains each piece and how they interact. For the wider fire safety picture, see Lab Manager’s guide to laboratory fire safety and NFPA 45.
What are the NFPA 45 laboratory unit classes?
NFPA 45 requires the laboratory owner to assign each laboratory unit a fire hazard classification based on the flammable and combustible liquids stored and used there. The four classes are A (high fire hazard), B (moderate), C (low), and D (minimal), with quantity limits that tighten from A to D.
Class | Fire hazard | Typical settings | Note |
A | High | Synthetic chemistry, process development, solvent-heavy work | Up to 10 gal Class I per 100 ft², or 20 gal Class I, II, and III combined |
B | Moderate | Many research and analytical labs | Lower limits than Class A |
C | Low | Undergraduate teaching labs are usually limited to Class C | Lower limits than Class B |
D | Minimal | High school teaching labs are examples | Lowest limits |
The Class A figures are reported in Lab Manager’s fire safety guide, and the teaching lab examples in an earlier Lab Manager article on safe storage of combustibles. Exact limits for each class depend on the edition, whether quantities are in use or in storage, whether the lab is sprinklered, and whether liquids are in approved cabinets, so consult the edition adopted for your building.
What is a control area?
A control area is a space bounded by fire-rated construction within which a building can store and use hazardous materials up to a maximum allowable quantity (MAQ). The building and fire codes limit both the number of control areas per floor and the share of the MAQ each one may hold.
Floor level | % of MAQ per control area | Control areas per floor |
1 | 100 | 4 |
2 | 75 | 3 |
3 | 50 | 2 |
4 to 6 | 12.5 | 2 |
7 to 9 | 5 | 2 |
10 and above | 5 | 1 |
Below grade 1 | 75 | 1 |
Below grade 2 | 50 | 1 |
Source: UW–Madison’s chemical storage guidelines. Newer code editions include an alternative path for higher education laboratories. The 2021 IFC’s Chapter 38, as adopted in one city’s code, allows larger percentages on upper floors when additional safeguards are met, along with a density limit of 8 gallons of Class I flammable liquids per 100 square feet, reduced on higher floors.
How do NFPA 45 and the fire code work together?
They apply at different scales, and a lab must meet both. A 2017 article in AIChE’s Chemical Engineering Progress explains that the IBC and IFC would allow 120 gallons of Class I flammable liquids per control area and up to four control areas on the first floor, or 480 gallons in total, while NFPA 45 separately limits quantities per 100 square feet of lab space. The same article notes that NFPA 45, in Section 8.2.4.1, requires each laboratory unit’s inventory to stay within the maximum allowable quantities in the applicable fire or building code.
- Start with the fire and building code. Identify control areas, their floor levels, and the resulting MAQs.
- Apply NFPA 45 within each lab unit. Check per-100 ft² and per-unit limits for the unit’s fire hazard class.
- Use the more restrictive answer. Whichever limit is reached first governs.
- Account for allowances. Codes typically allow larger quantities in sprinklered buildings and when liquids are in approved storage cabinets; confirm how your adopted code applies them.
- Track it with inventory. Without a current inventory by control area, compliance can’t be demonstrated.
What else does NFPA 45 require for storage?
- Container limits. NFPA 45 limits container sizes by liquid class and container type, which is why large solvent containers need approved safety cans or storage areas. The 2004 edition’s requirements also include limits on flammable gas cylinders in lab work areas.
- Approved storage. Flammable liquid storage cabinets and refrigerators designed for flammable storage; see our guide to flammable-safe refrigerators.
- Compatibility. Incompatible chemicals stored apart; see our storage compatibility chart.
- Pyrophoric protection. Flame-resistant lab coats where pyrophoric reagents are used outside a glove box; see our guide to choosing lab coats.
- Fire protection and ventilation. Requirements for sprinklers, fume hoods, and exhaust that depend on the lab’s classification and use.
Putting it into practice
- Classify each lab unit and record the classification.
- Map control areas and their floor levels with facilities or the fire marshal.
- Maintain an inventory that totals flammable and combustible liquids by lab unit and control area.
- Order only what you need; bulk discounts can push a lab over its limits.
- Review limits when labs move, change use, or are renovated, and when new code editions are adopted.
- In Canada, apply the National Fire Code of Canada and provincial adoptions, which follow similar principles but differ in detail.
Segregation, cabinets, and other storage basics are covered in our guide to lab chemical storage.
An NFPA 45 compliance checklist
- Each lab unit has a documented fire hazard class. The class sets quantity limits and other requirements. If no one has classified your labs, start with the highest-volume solvent users.
- Control areas are mapped and understood. Knowing which rooms share a control area, and on which floor, is essential for calculating limits. Facilities or the fire marshal can usually provide drawings.
- Inventory totals by lab unit and control area. Inventory systems should roll up flammable and combustible liquids by area, not just list bottles. Spreadsheets work for small sites; inventory software helps larger ones.
- The more restrictive limit governs. Check both NFPA 45 and the building or fire code, and apply whichever is lower. Document the calculation.
- Allowances for sprinklers and cabinets are applied correctly. Codes often allow increases for sprinklered buildings and approved cabinets, but conditions apply. Confirm with the authority having jurisdiction.
- Upper-floor labs are checked carefully. Floor-based reductions can cut allowable quantities dramatically. Labs above the third floor deserve particular attention.
- Purchasing supports compliance. Smaller, more frequent orders keep inventories within limits. Bulk purchasing should be checked against capacity.
- The applicable editions are confirmed. NFPA 45, the IBC, and the IFC are updated regularly and adopted locally on different schedules. Confirm editions with the authority having jurisdiction.
NFPA 45 tells you how much each lab can safely hold; the building code tells you how much the building can. Know both numbers, keep your inventory honest, and check the edition before you trust any figure, including the ones in this article.